DOYMA Curaflam® Rollit ISO Pro

Curaflam® Rollit ISOPro

DOYMA 25 Years Guarantee

Product benefits

  • tested zero clearances, even to other systems
  • insulated pipe conduits
  • retrospective fitting possible
  • space-saving and flexible

IBMB: P-3222/9781
IBMB: P-3637/8902

Uses

For sealing non-flammable insulated pipes

  • steel, case iron, stainless steel pipes up to an OD ≤ 813 mm*
  • copper pipes up to an OD ≤ 88.9 mm

*in solid wall/ceiling; in light partition wall for steel, cast iron and stainless steel pipes max. pipe OD ≤ 406 mm.

Licensed for the following insulations
  • PU with an insulation thickness of 40 mm to 100 mm [B1, B2]
  • synthetic rubber up to an insulation thickness of ≤ 100 mm [B1, B2]
  • mineral wool, glass wool, with melting point ≥ 500°C up to an insulation thickness ≤ 100 mm [A]
  • foam glass up to an insulation thickness ≤ 100 mm [A]
Assembly instructions
  • wall assembly
  • on both sides in walls made of porous concrete, concrete, masonry with a thickness ≥ 150 mm. The tape protrudes at least 50 mm from the wall on both sides.
  • retrospective fitting in front of the wall is possible, take care with the sheet metal cable coating!
  • on both sides in light partition walls with a thickness ≥ 75 mm (covering required on both sides). The tape protrudes at least 75 mm from the wall on both sides. Pay attention to sound insulation on both sides!
  • ceiling assembly
  • on both sides in ceilings made of porous concrete, concrete, masonry with a thickness ≥ 150 mm. The tape protrudes at least 50 mm from the ceiling on both sides.
  • retrospective fitting beneath and above the ceiling is possible, take care with the sheet metal coating!
  • installation with “zero clearance”. Seals around each pipe are permitted to come into contact with each other.
Test certificates

General appraisal certificates (abP) P-3222/9781-MPA BS and P-3637/8902-MPA BS.

Please see the certification for more details.

Firestops for flammable pipes

Curaflam® Rollit ISOPro
  • flexibly adjustable fire protection winding tape
  • storage box satisfies building site requirements
insulation material made of mineral wool, glass wool (melting point ≥ 500°C)
overlap 60 mm 100 mm 200 mm
total OD (pipe + insulation) length of the winding tape [mm] 1-ply, incl. overlap
53 500 - -
66 580
85 700
90 720
115 - 960
125 1020
137 1100
190 1440
215 - 1700
230 1780
250 1920
260 1980
285 2140
310 2300
315 2320
335 2440
345 2520

Table of necessary tape lengths