DOYMA Curaflam® Manschette ECOPro

Curaflam® Manschette ECOPro

DOYMA 25 Years Guarantee

Product benefits

  • zero clearance possible
  • 2 x 45° arches possible
  • installation flush-to-ceiling possible

DIBt: Z-19.17-1989

Use
  • plastic pipes PVC, PP, PE-HD, LDPE, PB, PE-X, ABS, ASA pipes OD ≤ 160 mm
  • sound-insulating sewage pipes OD ≤ 160 mm
    – Geberit Silent PP OD ≤ 110 mm
    – Geberit Silent dB 20 OD ≤ 160 mm
    – Wavin AS OD ≤ 160 mm
    – Wavin SiTech OD ≤ 160 mm
    – Rehau Raupiano Plus OD ≤ 160 mm
    – Friatec Friaphon OD ≤ 160 mm
    – Ostendorf Skolan OD ≤ 160 mm
  • multi-layer composite pipes
    – With aluminium insert OD ≤ 110 mm
    – From PEX for the transportation of flammable gases (as per DVGW G 600/G 260) OD ≤ 63 mm
Assembly of the firestop collar
  • both sides in front of walls made of porous concrete, concrete, masonry and light partition walls with thickness ≥ 100 mm
  • on one side under ceilings made of concrete with thickness ≥ 150 mm
  • completely flush fixed with mortar into ceilings
Licensing

The Curaflam® Manschette ECOPro is licensed by the Deutsches Institut für Bautechnik (DIBt) in accordance with Z-19.17-1989.

Please see the certification for more details.

Flexible Use

Screw the firestop collar to the wall / ceiling using the straps. Or fix the straps into the ceiling using mortar after bending the straps down or fix the firestop collar flush into the ceiling using mortar.

Firestops for flammable pipes

Curaflam® Manschette ECOPro
  • hinged fire protection seal
  • particularly cost-effective
pipe OD d [mm] OD of firestop collar b [mm] depth approx. c [mm] xxx for item numbers*
1 - 34 43 30 032
35 - 42 56 040
43 - 52 70 050
53 - 65 85 063
66 - 77 99 075
78 - 92 117 090
93 - 112 141 110
113 - 125 154 50 125
126 - 140 178 140
141 - 160 200 160

* Item number 3 23 1 xxx 000 00