DOYMA Curaflam® 49.950 BSRB, Curaflam® 49.950 BSRN

Curaflam® 49.950 BSRB

DOYMA 25 Years Guarantee

Product benefits

  • combination of sealing and firestop system
  • for visible areas, e.g. cleanrooms, hospitals, etc. Fire protection integrated fully into the wall / ceiling
  • many flammable / non-flammable pipe materials are possible
  • with acoustic decoupling

DIBt: Z-19.17-416IBMB: P-3025/0158

Uses
  • water-proof and gas-proof penetration in interior rooms with fire protection R 90 / R 120
  • for flammable pipes Curaflam® 49.950 BSRB
  • for non-flammable pipes Curaflam® 49.950 BSRN Both licensed up to OD 90 mm
This firestop consists of
  • 1 socket pipe
  • 2 screw caps with stainless steel cladding, ABS core and seal
  • 1 fire protection pack

For installation in walls with wall thicknesses ≥ 400 mm, 2 fire protection packs should be used.

Notes: For non-flammable pipe, insulate on both sides with thickness of 80 mm, length 700 mm, density 80 kg/m3. For wall thicknesses > 400 mm, 2 fire protection packs will be required.

Curaflam® accessories
  • adhesive (17010), pack volume 50 ml.
  • to adhere screw caps to the socket pipe.

The penetration is licensed for flammable pipes (Z-19.17-416) by the Deutsches Institut für Bautechnik (DIBt) and checked for nonflammable pipes (P-3025/0158).

Please see the license or test certification for more details.

Firestops for flammable / non-flammable pipes
Curaflam® 49.950 BSRB
  • seal is integrated invisibly into the wall / ceiling
  • for wet and dry rooms
pipe OD d [mm] socket OD D2 [mm]
5 - 13 32
14 - 15 40
16 - 23 54
24 - 28 70
29 - 35 80
36 - 43 90
44 - 49 103
50 - 61 115
62 - 77 135
78 - 90 151

L1 (standard length) [mm] 300; other lengths available.