DOYMA Curaflam® 12.500 BSRB, Curaflam® 12.500 BSRN

Curaflam® 12.500 BSRB

DOYMA 25 Years Guarantee

Product benefits

  • combination of sealing and firestop system
  • for visible areas, e.g. cleanrooms, hospitals, etc. Fire protection integrated fully into the wall / ceiling
  • many flammable / non-flammable pipe materials are possible
  • with acoustic decoupling

DIBt: Z-19.17-416IBMB: P-3025/0158

Uses
  • penetration in interior rooms with fire protection R 90 / R 120
  • for flammable pipes Curaflam® 12.500 BSRB
    – Licensed up to OD 160 mm
  • for non-flammable pipes Curaflam® 12.500 BSRN
    – Licensed up to OD 160 mm
This firestop consists of
  • 1 socket pipe
  • 2 rosettes
  • 1 seal
  • 1 fire protection pack

Notes: For non-flammable pipe, insulate on both sides with thickness of 80 mm, length 700 mm, density 80 kg/m3. For wall thicknesses > 400 mm, 2 fire protection packs will be required.

Curaflam® accessories
  • adhesive (17010), pack volume 50 ml.
  • to adhere screw caps to the socket pipe.
License / test certificate

The penetration is licensed for flammable pipes (Z-19.17-416) by the Deutsches Institut für Bautechnik (DIBt) and checked for nonflammable pipes (P-3025/0158).

Please see the license or test certification for more details.

Firestops for flammable / non-flammable pipes
Curaflam® 12.500 BSRB
  • seal is integrated invisibly into the wall / ceiling
  • for dry rooms
pipe OD d [mm] ID socket pipe D1 [mm] OD socket pipe D2 [mm] OD socket pipe D6 [mm]
bis 29 42 45 60
30 - 39 51 54 70
40 - 49 61 64 80
50 - 69 85 89 100
70 - 78 106 110 120
12.500 BSRB flammable pipes 12.500 BSRN non-flammable pipes
80 - 107 71 - 104 121 125 140
108 - 124 105 - 140 155 160 180
125 - 140 141 - 160 175 180 200
141 - 160 - 210 219 230

L1 (standard length) [mm] 300; other lengths available.